Selecting an Air Heater

The energy (kW) requirement is calculated from the following formula:

KW = SCFM × (Texit − Tinlet)
  2500

This formula estimates the heater size needed to raise air temperature from Tinlet to Texit at a given SCFM.

SCFM:
Tinlet:
Texit:
KW Required:
  

SCFM = Air flow in Standard* Cubic Feet per Minute
Tinlet = Inlet Air Temperature (°F) (typically 70°F)
Texit = Desired Exit Air Temperature (°F)

Example: Heating 10 SCFM from ambient temperature (70°F) to 800°F:

KW = 10 SCFM × (800°F − 70°F)  = 2.9 kW
  2500  

Conversion Formulas:
(Liters per Minute) / 28.3 = Cubic Feet per Minute
°C = 5/9 (°F − 32)
°F = 9/5 °C + 32

*Please refer to "Using an Air Heater" for an explanation of Standard flowrate.