A STUDY OF FROST HEAVE PREVENTION SYSTEMS

Thermalinc's Electric Heat Cable System vs. Hydronic (Glycol) Systems

Design, Failure Points & Monitoring

Frost heave prevention systems protect refrigerated slabs — freezer floors, cold storage warehouses, and similar structures — from ground freezing beneath the slab. Left unprotected, moisture in the subgrade forms ice lenses that expand the soil upward, cracking and buckling the structural slab above. Two mainstream approaches exist to keep the soil above freezing indefinitely: hydronic (glycol) systems, which circulate warmed fluid through buried piping, and Thermalinc's electric heat cable system, which runs self-regulating heating cable through buried conduit. This sheet compares the two approaches component-by-component, details the failure points inherent to each, and outlines the monitoring and protection architecture used on Thermalinc's electric system described below.

System Components — Side by Side

System ComponentHydronic (Glycol) SystemThermalinc's Electric Heat Cable System
Heat delivery mediumGlycol/water solution circulated through buried HDPE piping loopsSelf-regulating heat cable pulled into buried 3/4″ or 1″ conduit
Heat sourceElectric or waste-heat glycol heater, boiler, or refrigeration heat-reclaim packageDirect electric resistance in the cable itself
Fluid handlingCirculator pump, expansion tank, air separator, fill/purge valves, glycol concentration maintenanceNone required — no fluid in the system
Distribution / zoningBalancing manifold with flow meters/balancing valves per loopPLC-controlled circuits switched by solid-state relays (SSR)
Protection devicesPressure relief, low-flow interlock on heater, freeze protection for mechanical room equipmentMain disconnect, dedicated breaker per circuit, GFI (ground-fault) protection per circuit
MonitoringSoil temperature sensors; optional flow/pump statusSoil/floor temperature sensors with low-temp alarm and event-duration history; per-circuit end-of-line (EOL) voltage sensing for SSR fault detection in both directions; fault logging
Operator interface / annunciationTypically limited to building management system (BMS) integration, if presentColor interactive display, 98 dB audible horn, and a red stack light that remains illuminated after the horn is silenced for as long as the fault persists
Mechanical room footprintPump, heater, expansion tank, air separator, manifold, fill stationPLC panel, breakers/GFI, SSR bank — no fluid components

Hydronic (Glycol) System — Failure Points

A hydronic system introduces a closed fluid loop with mechanical, hydraulic, and chemical elements — each an additional point where the system can degrade or fail, in addition to the electrical components common to any heated system.

Failure PointWhat Can Go WrongConsequence
Glycol leak (buried loop)Pinhole leak, fitting failure, or fusion joint defect in buried HDPE pipingGlycol lost to soil (environmental/reporting concern), gradual pressure/flow loss, slow-developing cold spot that may not be noticed for a long time — buried leaks are difficult and costly to locate and repair
Circulator pump failureBearing wear, seal failure, electrical/motor fault, impeller wear from glycolLoss of flow to entire manifold — all loops lose heat delivery simultaneously unless a standby pump is installed
Air lock / inadequate air separationTrapped air not purged during fill, or air separator undersized/fouledLocalized flow reduction or pump cavitation/noise; heater hot-spot risk if air reaches the element
Loss of flow at heaterPump failure, closed valve, clogged strainer, or flow-switch fault not caughtHeater element can overheat or scorch fluid without adequate flow across it — safety and reliability risk
Manifold balancing valve driftValve setting changes over time (vibration, service work, unqualified adjustment)One or more loops under- or over-flowed; far end of an under-flowed loop is a potential cold spot
Expansion tank failureBladder rupture, loss of pre-charge, waterlogged tankLoss of system pressure control; can cause relief valve discharge, pump cavitation, or air ingress
Glycol degradation over timeConcentration drift, additive depletion, oxidation from air contaminationReduced freeze protection margin, increased corrosion risk to pump/heater/piping — requires periodic testing (refractometer) and fluid maintenance
CorrosionImproper inhibitor package for wetted metals (aluminum, brass, cast iron, steel)Internal component degradation, leaks, and reduced heat transfer over the life of the system
Freeze exposure of mechanical equipmentPump, heater, manifold, or exposed header piping located in or near an unconditioned spaceThe freeze-protection equipment itself becomes vulnerable to freezing if not properly located or protected
Header run heat lossUn-modeled or underestimated heat loss between mechanical room and slab loop fieldGlycol arrives at the manifold below design temperature, undermining the loop delta-T the whole system was sized around
Single point of failure at manifold/pumpOne pump and one heater typically serve the entire loop field unless redundancy is designed inA single component failure can take the entire frost-heave protection system offline at once
Loss of incoming powerUtility outage or upstream electrical faultPump and heater both stop — a limitation shared with the electric system, which also cannot operate without power

Thermalinc's Electric Heat Cable System — Failure Points

An electric system removes the fluid loop entirely — no pump, no glycol, no expansion tank, no air separator, no manifold balancing. The remaining failure points are electrical in nature and, as detailed below, are directly monitored and self-diagnosing by design.

Failure PointWhat Can Go WrongConsequenceCorrection
Cable damage in conduitPhysical damage during installation or from ground movementDetected as a failed-open condition (no far-end voltage on a call for heat) the same way an SSR failure is detectedEasily replaced cable — simply pull the old cable out of the conduit and pull in new, readily available cable. No trenching or slab work
SSR failed shorted (conducting)Solid-state relay fails in the "on" stateCircuit stays energized even when the PLC is not calling for heat — detected immediately by far-end voltage present with no call for heat, alarmed for replacementReplace the failed SSR at the panel; the fault is isolated to that one circuit, so no field work or cable access is needed
SSR failed open / cable or splice faultSSR fails open, cable is damaged, or a splice/connection degradesNo voltage at the far end while the PLC is calling for heat — detected immediately and alarmed as a loss-of-heat condition on that circuitSwap the SSR first, since it's the simplest check; if voltage still doesn't reach the far end, the fault is in the cable or a splice and is repaired or the cable segment is replaced through conduit
Ground fault on a circuitInsulation damage or moisture ingress at a cable or connection pointCircuit-specific GFI protection trips that circuit — isolates the fault to a single zone rather than the whole system, and is independently monitoredLocate and repair the insulation break or moisture entry point, then reset the GFI for that circuit; the rest of the system stays online the entire time
Overcurrent on a circuitCable or connection fault drawing excess currentDedicated breaker per circuit trips and isolates only the affected zoneInspect and correct the cause of the excess current draw, then reset the breaker for that circuit only
Loss of incoming powerUtility outage or upstream electrical fault, ahead of the main disconnectWith no incoming power, the PLC, alarms, and display all lose power along with the heat cable circuits — there is no local alarm during the outage itself. This is a limitation shared with the hydronic system, whose pump and heater also stop without powerRestore utility power or correct the upstream electrical fault; both system types resume normal operation automatically once power is back, no reconfiguration needed
Floor/soil temperature trending toward freezingAny upstream cause (SSR, cable, breaker) or an undersized zone, while the system has powerIndependently monitored floor temperature sensor with low-temperature alarm — a direct check that doesn’t depend on the electrical circuit’s own self-reporting being correct. Like the rest of the system, the sensor itself needs power to reportUse the fault log and per-circuit voltage sensing to identify which upstream circuit or component is actually responsible, then apply the specific correction above for that fault

Protection & Monitoring Architecture (Electric System)

Every circuit in this electric system is protected and independently monitored across multiple layers, from the main disconnect down to direct floor temperature sensing, with all faults logged and clearly annunciated to an operator — giving electrical-fault detection, physical confirmation that the protected area is staying above the freeze-risk threshold, and a permanent record of any event.

Protection / Monitoring LayerFunction
Main disconnectA single point electrical connection for the system — one main switch that disconnects power, with lockout/tagout (LOTO), providing safe shutdown and lockout of the whole system for service
Dedicated circuit breaker — per circuitOvercurrent protection isolated to a single zone; a fault on one circuit does not affect the others
GFI protection — per circuitGround-fault protection isolated to a single zone, independently monitored by the PLC
Far-end voltage sensing — per circuitConfirms actual cable energization at the far end of the run, catching both an SSR failed shorted and an SSR failed open or cable/connection fault
Floor/soil temperature sensor — low alarmIndependent, ground-sensing confirmation that each zone is operating within the safe temperature threshold
Fault loggingEvery fault is recorded with its precise location — building a permanent, reviewable fault history rather than relying on someone having witnessed the event
Troubleshooting guide — fault historyA brief troubleshooting guide is included within the fault history to help correct the problem
Low-temperature event timer/historyRecords and timestamps the duration of any low-temperature condition, so a marginal or intermittent event is captured and documented, not just a hard alarm trip
Color interactive displayLocal operator interface for real-time system status, circuit-by-circuit conditions, and review of fault and temperature history without needing a separate laptop or software
98 dB audible hornSounds immediately on any fault condition to ensure the alarm is noticed in an active facility environment
Stack light — red, latching after horn silenceSilencing the horn does not clear the alarm — the red stack light remains illuminated for as long as the fault condition still exists, so a silenced horn can never be mistaken for a resolved fault
Digital output — BMS interlockSeparate digital output for interlocking with building maintenance systems
Peak setback — remote inputRemote input provides setback temperature operation during peak electrical hours
Sensor fault alarmAlarm indication if any temperature sensor fails
PLC-based supervisory controlCentralizes all of the above into a single point of alarm annunciation, display, and historical/trend logging

Summary: Why This Matters

Hydronic Systems

  • More components — pump, heater, expansion tank, air separator, manifold, fill/purge system — means more individual points of potential failure
  • A glycol leak in a buried loop is difficult to locate, costly to repair, and raises environmental/reporting considerations
  • A single pump or heater failure can take the entire loop field offline unless standby equipment is designed in
  • Requires ongoing fluid maintenance — concentration testing, corrosion inhibitor monitoring — for the life of the system
  • The freeze-protection equipment itself (pump, heater, manifold) must be protected from freezing if located in or near an unconditioned space
  • Primary advantage: can use waste heat from refrigeration equipment, which may lower operating cost on very large installations

Thermalinc's Electric Heat Cable System

  • No fluid, no leak risk into the soil, no pump, no expansion tank, no glycol maintenance
  • Circuit-level isolation — a fault on one zone (breaker trip, GFI trip, cable fault) does not affect the others
  • Full-coverage, self-diagnosing fault detection: far-end voltage sensing catches both an SSR failed shorted and an SSR failed open or cable/connection fault
  • Independent floor/soil temperature monitoring with low-temperature alarm provides ground-truth confirmation, regardless of what any single electrical component reports
  • Main disconnect, per-circuit breakers, and per-circuit GFI protection give layered, zone-isolated protection consistent with standard electrical safety practice
  • Built-in fault logging and low-temperature event history create a permanent, reviewable record
  • Color interactive display, 98 dB horn, and a latching red stack light ensure faults are noticed immediately and cannot be forgotten once the horn is silenced
  • Simpler mechanical room footprint — no fluid-handling equipment to install, commission, or service
Back to the overview.
This is one piece of the full freezer floor frost heave prevention system.  Back to Freezer Floor Frost Heave Prevention →